    XGJD-II SF6 Gas Density Relay Calibrator
    Product Overview
    The XGJD-II SF6 Gas Density Relay Calibrator is a high-precision portable testing instrument designed for the field calibration and verification of SF6 gas density relays and pressure gauges. The instrument uses precision imported components, a high-accuracy pressure sensor, high-resolution A/D and D/A converters, a high-performance 32-bit ARM microcontroller and a high-speed signal processing chip from TI.
    The XGJD-II can automatically measure the pressure corresponding to relay contact actions at the current ambient temperature and convert the measured pressure into the equivalent standard pressure at 20°C. The instrument automatically completes pressure-temperature compensation, test data storage, printing and test result analysis without requiring manual intervention.
    The instrument is designed with high accuracy, high stability and high reliability. It is suitable for on-site calibration of SF6 gas density relays, pressure gauges and related monitoring devices used in high-voltage switchgear and SF6-insulated electrical equipment.

     

    Key Features
    • Uses a 32-bit ARM microcontroller and high-speed TI signal processing chip for integrated measurement and control.
    • High-precision electromechanical integrated design provides good repeatability and reliable operation.
    • Large-screen Chinese LCD display provides clear visualization of measurement parameters and instrument status.
    • Rotary mouse control with one-button operation provides a simple and intuitive user interface.
    • Automatically measures pressure and converts the measured value to the equivalent pressure at 20°C.
    • Automatically compensates for the dynamic relationship between pressure and ambient temperature.
    • Displays the pressure under the current ambient temperature, equivalent pressure at 20°C and ambient temperature simultaneously.
    • Automatically completes the entire calibration process without manual intervention.
    • Eliminates complicated manual adjustment of the test gas circuit.
    • Automatically identifies faults occurring during the testing process.
    • Provides Chinese report-style printing of test results.
    • Performs intelligent analysis of test results.
    • Stores up to 50 test records and provides power-failure data protection.
    • Previously stored test results can be queried and printed at any time.
    • No constant-temperature chamber is required. Calibration can be performed within the valid ambient temperature range.
    • Multiple transition adapters are supplied, allowing most SF6 density relays to be tested without removing them from the switchgear.
    • Extremely low SF6 gas consumption reduces gas waste and testing costs.
    • Low gas consumption helps minimize environmental impact during testing.
    • System date and time can be modified online.
    • System pressure can be modified and corrected on site.
    • Core components use precision imported components for reliable performance.
    • Supports simultaneous testing of one alarm signal and two interlock signals.
    • Portable design makes the instrument convenient for field inspection, maintenance and calibration.

     

    Working Principle
    The XGJD-II calibrator applies controlled pressure to the SF6 gas density relay under test while simultaneously measuring the pressure and ambient temperature with high-precision sensors.
    When the density relay reaches a specified alarm or locking action point, the instrument detects the corresponding contact signal and records the pressure at the current ambient temperature.
    Because SF6 pressure varies with temperature, the instrument automatically converts the measured pressure under the actual test temperature into an equivalent standard pressure at 20°C. This allows the test result to be compared consistently with the rated pressure values of the SF6 density relay.
    The automatic pressure-temperature compensation eliminates the need for manual calculation and reduces errors associated with traditional field calibration methods.

     

    SF6 Gas Density Relay Calibration Process
    Connect the appropriate transition adapter and test line to the SF6 density relay.
    Connect the relay alarm and interlock contacts to the instrument.
    Set or verify the relevant test parameters.
    The instrument automatically controls and measures the test pressure.
    When the relay reaches the specified action point, the instrument automatically detects the corresponding electrical signal.
    The current pressure and ambient temperature are recorded automatically.
    The instrument converts the measured pressure to the equivalent pressure at 20°C.
    The test result is automatically analyzed and stored.
    Test results can be printed directly through the built-in micro printer.
    This automated process significantly reduces manual operations and improves the efficiency and repeatability of SF6 density relay calibration.

     

    Technical Specifications
    Parameter Specification
    Power Supply AC 220V, 50Hz
    Instrument Power 50W
    Accuracy Class 0.2
    Pressure Display Resolution 0.001MPa
    Pressure Calibration Range 0–1.0MPa
    Ambient Temperature Display Resolution 0.1°C
    Ambient Temperature Measurement Range -50°C to 150°C
    Operating Humidity ≤90% RH
    Calibration Objects Single alarm, single interlock, single alarm + single interlock, single alarm + double interlock
    Display 320 × 240 graphic dot-matrix monochrome LCD
    Operation Rotary mouse / one-button control
    Printer High-speed micro printer
    Printing Method Chinese report-style printing
    Data Storage Up to 50 test results
    SF6 Density Display Pressure at measured ambient temperature and equivalent pressure at 20°C
    Main Unit Dimensions 365mm × 300mm × 220mm
    Accessory Case Dimensions 400mm × 370mm × 200mm
    Instrument Weight 8kg
     

    Applications
    The XGJD-II SF6 Gas Density Relay Calibrator is designed for testing and calibration of:
    • SF6 gas density relays
    • SF6 pressure relays
    • SF6 pressure gauges
    • SF6 density monitoring devices
    • Alarm contact systems
    • Locking/interlock contact systems
    • SF6 high-voltage switchgear
    • SF6-insulated electrical equipment
    • Gas-insulated switchgear maintenance systems

     

    Application Scenarios
    SF6 Switchgear Field Calibration
    The portable design allows technicians to perform SF6 density relay calibration directly at the installation site without transporting the equipment to a laboratory.
    High-Voltage Switchgear Maintenance
    The instrument can verify alarm and interlock action points of SF6 density relays during routine maintenance and preventive inspection.
    Relay Calibration Without Removal
    With multiple transition adapters, most applicable SF6 density relays can be tested without removing the relay from the switchgear, significantly reducing maintenance time.
    Temperature-Compensated Testing
    The automatic conversion from actual ambient temperature pressure to the equivalent pressure at 20°C makes the instrument suitable for field testing under varying environmental temperatures.
    Pressure Gauge Verification
    The XGJD-II can also be used for pressure calibration and verification of applicable SF6 pressure gauges.

     

    Calibration Object Types
    Calibration Object XGJD-II Support
    Single Alarm ✓
    Single Interlock ✓
    Single Alarm + Single Interlock ✓
    Single Alarm + Double Interlock ✓
    SF6 Density Relay ✓
    SF6 Pressure Gauge ✓
     

    Advantages Compared with Manual Calibration
    Item XGJD-II Automatic Calibration Traditional Manual Calibration
    Pressure Measurement Automatic Manual
    Temperature Measurement Automatic Manual or separate measurement
    20°C Pressure Conversion Automatic Manual calculation
    Pressure-Temperature Compensation Automatic Manual
    Gas Circuit Adjustment Automatic Manual
    Test Result Recording Automatic Manual
    Test Data Printing Built-in printer Usually requires manual recording
    Data Storage Up to 50 records Limited/manual
    Fault Detection Automatic Operator dependent
    Constant-Temperature Chamber Not required May be required
    Field Calibration Supported More complicated
    Relay Removal Usually not required with suitable adapter Often required depending on method
     

    FAQ
    What is the XGJD-II SF6 Gas Density Relay Calibrator used for?
    The XGJD-II is designed for field calibration and verification of SF6 gas density relays and applicable pressure gauges, including their alarm and interlock action points.
    Does the XGJD-II automatically compensate for temperature?
    Yes. The instrument automatically measures the ambient temperature and converts the measured pressure to the equivalent pressure at 20°C, eliminating manual pressure-temperature calculations.
    Is a constant-temperature chamber required?
    No. The XGJD-II can perform calibration within its specified ambient temperature measurement range without requiring a constant-temperature chamber.
    Can SF6 density relays be tested without removing them?
    Yes. The instrument is supplied with multiple transition adapters, allowing most applicable SF6 density relays to be calibrated on site without removing them from the switchgear.
    What is the pressure calibration range?
    The pressure calibration range is 0–1.0MPa, with a pressure display resolution of 0.001MPa.
    What is the accuracy of the XGJD-II?
    The instrument has an accuracy of Class 0.2.
    How many test records can be stored?
    The XGJD-II can store up to 50 test results and provides power-failure data protection.
    Can test results be printed?
    Yes. The instrument has a built-in high-speed micro printer and can print test results in Chinese report format.
    What types of relay contacts can be tested?
    The instrument supports single alarm, single interlock, single alarm + single interlock, and single alarm + double interlock configurations.
    What is the ambient temperature measurement range?
    The ambient temperature measurement range is -50°C to 150°C, with a display resolution of 0.1°C.
    How does the XGJD-II reduce SF6 consumption?
    The automatic pressure control and calibration process require very little SF6 gas, helping reduce gas consumption, testing costs and unnecessary SF6 emissions.
     

  • FAQ
    What is the XGJD-II SF6 Gas Density Relay Calibrator used for?
    The XGJD-II is designed for field calibration and verification of SF6 gas density relays and applicable pressure gauges, including their alarm and interlock action points.
    Does the XGJD-II automatically compensate for temperature?
    Yes. The instrument automatically measures the ambient temperature and converts the measured pressure to the equivalent pressure at 20°C, eliminating manual pressure-temperature calculations.
    Is a constant-temperature chamber required?
    No. The XGJD-II can perform calibration within its specified ambient temperature measurement range without requiring a constant-temperature chamber.
    Can SF6 density relays be tested without removing them?
    Yes. The instrument is supplied with multiple transition adapters, allowing most applicable SF6 density relays to be calibrated on site without removing them from the switchgear.
    What is the pressure calibration range?
    The pressure calibration range is 0–1.0MPa, with a pressure display resolution of 0.001MPa.
    What is the accuracy of the XGJD-II?
    The instrument has an accuracy of Class 0.2.
    How many test records can be stored?
    The XGJD-II can store up to 50 test results and provides power-failure data protection.
    Can test results be printed?
    Yes. The instrument has a built-in high-speed micro printer and can print test results in Chinese report format.
    What types of relay contacts can be tested?
    The instrument supports single alarm, single interlock, single alarm + single interlock, and single alarm + double interlock configurations.
    What is the ambient temperature measurement range?
    The ambient temperature measurement range is -50°C to 150°C, with a display resolution of 0.1°C.
    How does the XGJD-II reduce SF6 consumption?
    The automatic pressure control and calibration process require very little SF6 gas, helping reduce gas consumption, testing costs and unnecessary SF6 emissions.
     

     
Products
Analytical instruments
Physical property test
Environmental monitoring and analysis
Lab general equipment
About us
About this website
Our service
Product purchase
Contact Us

Newsletter

Make Sure you dont miss interesting happenings by joining our newsletter program.

Contact Us
+86-18620722006
instruments@instrumentstrade.com