| Parameter | Specification |
| Voltage Measurement Range | 5V~400V |
| Voltage Measurement Accuracy | Class 0.2 |
| Current Measurement Range | 0.1A~20A |
| Current Measurement Accuracy | Class 0.2 |
| Operating Voltage Without External Regulator | AC220V |
| Working Temperature | -10℃~50℃ |
| Relative Humidity | ≤85%RH |
| Power Supply | AC220V ±10% |
| Power Frequency | 50Hz ±10Hz |
| Measurement Functions | Short circuit impedance, zero-sequence impedance, inductance |
| Display | Large LCD screen |
| Data Storage | Supported |
| Communication Interface | RS232, USB |
| Operation Mode | Automatic / Manual testing |
| Impedance Error Range | Evaluation |
| Within ±2% | Transformer can operate normally |
| ±2%~±5% | Regular inspection recommended |
| Greater than ±5% | Transformer should be removed from operation for inspection |
| Comparison Item | GHRB-I Transformer Short Circuit Impedance Tester | Traditional Testing Method |
| External Voltage Regulator | Not required | Usually required |
| Testing Operation | Automatic measurement | More manual operations |
| Wiring Method | One-time connection | Repeated wiring adjustment |
| Three-Phase Testing | Automatic support | Manual switching often required |
| Data Processing | Automatic calculation and storage | Manual recording required |
| Portability | Compact and lightweight | Larger equipment setup |