| Parameter | Specification |
|---|---|
| Model | BWR-04JJ(TH) |
| Output Signal | Dual DC 4–20mA standard current signals |
| Working Conditions | Ambient temperature −40 to +55°C; RH ≤95% |
| Measuring Range | 0–150°C |
| Accuracy Class | Class 2.0 |
| Maximum Permissible Error at Test Point | ±3°C |
| Adjustable Switches | 4 groups |
| Switch Setting | Freely adjustable throughout the full measuring range |
| Switch Action Error | ±2°C |
| Switch Differential | 6 ± 2°C |
| Switch Rating | AC 220V / 5A |
| Temperature Bulb | Φ14 × 150 mm |
| Mounting Thread | M27 × 2 mm |
| Capillary Length | 6 m |
| Protection Rating | IP55 |
| Installation | Two available instrument installation configurations |
| Parameter | Specification |
|---|---|
| Model | XMZ-155 |
| Input Signal | DC 4–20mA standard current signal |
| Output Signal | DC 4–20mA standard current signal |
| Working Conditions | 0–50°C; RH ≤85% |
| Power Supply | AC 220V / 50Hz |
| Accuracy Class | Class 1.0 |
| Display | LCD |
| Mounting Type | Embedded / panel-mounted |
| Dimensions | 160 × 80 × 85 mm |
| Panel Cutout | 152+1 × 76+1 mm |
| Feature | BWR-04JJ(TH) | Conventional Transformer Temperature Indicator |
|---|---|---|
| Measuring Principle | Additional temperature-rise principle | Basic temperature indication |
| Measuring Range | 0–150°C | Application dependent |
| Accuracy | Class 2.0 | Application dependent |
| Control Switches | 4 adjustable groups | Usually limited |
| Switch Setting | Full-range adjustable | Usually limited |
| Cooling Control | Supported | Usually requires additional control equipment |
| Alarm Function | Supported | Depends on system configuration |
| Overtemperature Trip | Supported | Depends on system configuration |
| Analog Output | Dual 4–20mA | Depends on model |
| Outdoor Operation | Supported | Depends on protection design |
| Protection Rating | IP55 | Application dependent |
| Digital Display | XMZ-155 compatible | Depends on configuration |